Pump Protection FTW360 | Liquipoint T FTW31 | Liquipoint T FTW32 | Double rod probe 11362Z | Triple rod probe 11363Z | One rod probe 11371 | One rod probe 11375 | One rod probe 11375Z | One rod probe 11375ZF | One rod probe 11961 | One rod probe 11961Z | One rod probe 11961ZF | |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
|
Measuring principle
|
Conductive | Conductive | Conductive | Conductive | Conductive | Conductive | Conductive | Conductive | Conductive | Conductive | Conductive | Conductive |
Characteristic / Application
|
Compact limit switch for pump protection Active build up compensation Flush mounting | Compact rod probe with multipoint detection, possible up to 5 switch points. Simple rope shortening | Compact rope probe mit with multi point detection possible up to 5 switch points. Simple rope shortening possible | Double rod probe with high-class media contacting wetted parts | Triple rod probe with high-class media contacting wetted parts | One rod probe. Simple rod shortening or rod change on location | One rod probe for high temperature and high pressure. Corrosion resistant | One rod probe for high temperature and high pressure. corrosion resistant | One rod probe for high temperature and high pressure. Corrosion resistant | One rod probe for high and extremely low temperature and high pressure. Corrosion resistant | One rod probe for high and etremely low temperature an high pressure. Corrosion resistant | One rod probe for high an extremely low temperatures an high pressure. Corrosion resistant |
Supply / Communication
|
21V ... 253V AC 20V ... 200V DC |
DC PNP 10,8V ... 45V Relay 20V ... 230V AC Relay 20V ... 55V DC |
DC PNP 10,8V ... 45V Relay 20V ... 230V AC Relay 20V ... 55V DC |
Relay | Relay | Relay | Relay | Relay | Relay | Relay | Relay PFM |
Relay |
Ambient temperature
|
-20 °C ... 60 °C | -40 °C ... 70 °C | -40 °C ... 70 °C | -20 °C ... 80 °C | -20 °C ... 80 °C | -20 °C ... 120 °C | -40 °C ... 80 °C | -40 °C ... 80 °C | -40 °C ... 80 °C | -200 °C ... 250 °C | -200 °C ... 250 °C | -20 °C ... 65 °C |
Process temperature
|
-20 °C ... 100 °C | -40 °C ... 100 °C | -40 °C ... 70 °C | -40 °C ... 150 °C | -40 °C ... 150 °C | -20 °C ... 120 °C | -40 °C ... 200 °C | -40 °C ... 135 °C | -40 °C ... 135 °C | -200 °C ... 250 °C | -200 °C ... 250 °C | -20 °C ... 65 °C |
Process pressure absolute / max. overpressure limit
|
Vacuum ... 10 bar | Vacuum ... 10 bar | Vacuum ... 10 bar | Vacuum ... 30 bar | Vacuum ... 30 bar | Vacuum ... 10 bar | Vacuum .... 50 bar | Vacuum ... 50 bar | Vacuum .... 50 bar | Vacuum ... 160 bar | Vacuum ... 160 bar | Vacuum ... 160 bar |
Min. density of medium
|
min. 10 uS | min. 10 uS | min. 10 uS | min. 10 uS | min. 10 uS | min. 10 uS | min. 10 uS | min. 10 uS | min. 10 uS | min. 10 uS | min. 10 uS | min. 10 uS |
Wetted parts
|
1.4571, PTFE | 316L, PP, PPS | 316L, FEP, PPS | PTFE, PFA, 316 TI, Alloy B/C4, Titan, Tantal, Monel | PTFE, PFA, 316 TI, Alloy B/C4, Titan, Tantal, Monel | PFA, 316TI | PTFE, 316TI | PTFE, 316TI | PTFE, 316TI | Ceramic, 316TI | Ceramic, 316TI | Ceramic, 316TI |
Max. tensile strength
|
1000 N | 500 N | ||||||||||
Process connection
|
G3/4A | G 1 1/2 PPS NPT1 1/2" |
G 1 1/2 PPS NPT1 1/2" |
G 1 1/2A NPT1 1/2" Flange DIN /ANSI |
G 1 1/2A NPT1 1/2" Flange DIN /ANSI |
G 1 1/2A Einschwei?stutzen |
G 1 1/2A |
G 1 1/2A |
G 1 1/2A |
G 1/2A |
G 1/2A |
G 1/2A |
Hygienic
|
Flush mounting | |||||||||||
Sensor length
|
0,1m ... 4m | 0,25m ... 15m | 0,1m ... 4m | 0,1m ... 4m | 0,05m ... 2m | 0,05m ... 2m | 0,05m ... 2m | 0,05m ... 2m | 0,1m ... 2m | 0,1m ... 2m | 0,1m ... 2m | |
Output
|
Relay | DC PNP Relay |
DC PNP Relay |
Relay | Relay | Relay | Relay | Relay | Relay | Relay | Relay | Relay |
Certificates / Approvals
|
ATEX WHG Leckage Detection Certificate |
ATEX WHG Leakage Detection certificate |
ATEX WHG |
ATEX WHG |
ATEX |
ATEX |
ATEX WHG |
ATEX WHG |
||||
Specialities
|
CIP suiteable | prod_comp_text_23795 | ||||||||||
Application limits
|
Observe minimum medium conductivity | Observe min. medium conductivity | Observe min. medium conductivity | Observe min medium conductivity | Observe min. medium conductivity | Observe min. medium conductivity | Observe min. medium conductivity | observe min. medium conductivity | Observe min. medium conductivity | Observe min. medium conductivity | Observe min. medium conductivity | Observe min. medium conductivity |
Instrumentation
|
Compact Separate |
Compact Separate |
Separate | Seperate | Seperate | Seperate | seperate | Seperate | Seperate | Separate | ||
Electronic insert
|
PFM: EC17Z, EC27Z | |||||||||||
Components
|
Transmitter: FTW325 | Transmitter: FTW325 | Transmitter: FTW325 | Transmitter: FTW325 | Transmitter: FTW325 | Transmitter: FTW325 | Transmitter: FTW325 | Transmitter: FTW325 | Transmitter: FTW325 | Transmitter: PFM: FTC520Z, FTC521Z, FTC625, FTC470Z, FTC471Z Relay: FTW325 | Transmitter: FTW325 |